As AI Processor Packages Grow, MES Publishes Guidance on When Tighter Cold Plate Flatness Adds Cost Without Improving Cooling
PR Newswire
COLUMBUS, Ohio, Nov. 18, 2026
MES Advises Data Center Liquid Cooling Teams to Specify Cold Plate Flatness and Surface Finish Together
COLUMBUS, Ohio, Nov. 18, 2026 /PRNewswire/ -- Data center engineering and sourcing teams that tighten cold plate flatness tolerances may be adding manufacturing cost without a meaningful cooling benefit, according to new guidance published by MES, Inc., a global manufacturing sourcing and supply chain company serving Fortune 500 OEMs. The guidance compares the flatness and surface finish that five machining processes can typically hold and outlines what to specify on direct-to-chip cold plate drawings.
The challenge grows with AI processor packages. Holding 0.025 mm across a 30 mm die works out to 1 part in 1,200. Across a 70 mm die, the same tolerance is 1 part in 2,800, while residual stress relaxation, heat from the cut and fixture distortion act over more than twice the distance.
"As AI packages get larger, it's natural to want a tighter number on the cold plate drawing," said Hiten Shah, President and CEO of MES. "We'd start with the thermal model. If it doesn't show a measurable benefit, a tighter tolerance can add cost without improving cooling."
Cost rises in steps. Moving a callout from 0.025 mm to 0.015 mm can shift the contact face from precision CNC machining to grinding or dedicated fly cutting, adding setup, fixturing and inspection costs. MES's guidance identifies 0.025 mm across the die contact footprint as a good working specification for most direct-to-chip applications, with the final tolerance set by the thermal model.
Flatness and surface finish affect the interface differently. Thermal interface material (TIM) typically forms a layer 25 to 75 microns thick and conducts a few W/m•K, compared with about 388 W/m•K for copper. A plate dished 0.040 mm can add up to 40 microns of TIM locally, while a flat but rough face can leave microscopic voids. The guidance describes 0.4 to 0.8 µm Ra as a useful working range for many contact faces, depending on the TIM and contact pressure, and suggests specifying both Ra and Rz on critical die interfaces.
"A cold plate can pass a flatness check and still add thermal resistance if surface finish was never specified," said Brad Layne, Engineering Manager at MES. "We recommend calling out flatness and surface finish together, and measuring flatness across the die footprint, where it affects heat transfer."
Machining sequence belongs on the drawing. As-brazed flatness commonly runs 0.100 to 0.250 mm because a vacuum braze cycle can relieve residual stress and change the shape of the base. The guidance recommends machining the mounting face after brazing and calling out that sequence as a process note.
MES supplies copper and aluminum cold plates through a manufacturing network spanning eight countries. Its engineering team reviews drawings before tooling begins, and parts are verified by CMM at the source.
The full guidance, including process comparison tables and a contact face specification checklist, is available at https://mesinc.net/why-a-tighter-flatness-spec-can-double-cold-plate-cost/
About MES, Inc.
Headquartered in Lewis Center, Ohio, MES, Inc. is a global manufacturing sourcing and supply chain company serving OEMs in electrical and energy, automotive, robotics, lighting, and construction and agriculture. MES manages sourcing, engineering, quality and delivery across a global supplier network with operations in the United States, Mexico, Poland, India, Vietnam, China and beyond. MES has been ISO 9001:2015 certified since 2009 and is NMSDC certified. Learn more at https://mesinc.net.
View original content to download multimedia:https://www.prnewswire.com/news-releases/as-ai-processor-packages-grow-mes-publishes-guidance-on-when-tighter-cold-plate-flatness-adds-cost-without-improving-cooling-302944112.html
SOURCE MES, Inc.